Three-Dimensional Pulse Width Modulation Techniques for Three-Phase Four Leg Voltage Source Converters
Mohamed Elbar, Imad Merzouk, Mohamed Mounir Rezaoui, Noureddine Bessous
Abstract
This paper presents a new control strategy to improve the performance of shunt active power filter (SAPF) in three-phase four-wire system when operating under an unbalanced system. A control method based on the instantaneous power theory have been used and discussed. On the other side, a three-dimensional hysteresis current controller is used to track the compensated current references. This scheme requires the service of a phased-locked loop (PLL) to make the system insensitive to the distortions that are generally present in the utility voltages. The performance of the proposed topology under the used control approach has been finally discussed through the obtained simulation results.
Details
| Original language | English |
|---|---|
| Journal | Algerian Journal of Signals and Systems |
| Volume | 5 |
| Issue number | 3 |
| Pages | 153-158 |
| ISSN | 2543-3792 · 2676-1548 |
| DOI | 10.51485/ajss.v5i3.111 |
| Publication status | Published — 15 September 2020 |
Keywords
Fingerprint
- Power Quality and Harmonics
- Multilevel Inverters and Converters
- Microgrid Control and Optimization
- shunt active power filter
- three-phase four-wire system
- unbalanced systems
- instantaneous power theory
- hysteresis current control
- phase-locked loop
- harmonic compensation
- power quality
- Electrical and Electronic Engineering
- Control and Systems Engineering
- Engineering