LED lamp modelling for harmonic studies in distribution systems

الملخّص

Energy saving policies have boosted the use of light emitting diode (LED) lamps in distribution networks. These lamps are non‐linear loads which inject harmonic currents into the distribution system, which has led to a decrease in the system power quality. Study of the modelling of these lamps would allow the prediction of harmonic emissions into distribution systems. This study presents a frequency‐domain LED lamp model for harmonic emission calculation, together with a simple estimation procedure for model parameter determination from experimental measurements. Both were validated by laboratory tests. Finally, an application illustrates the effect of widespread use of LED lamps in a typical distribution system and allows LED lamp models to be compared.

التفاصيل

اللغة الأصليةEnglish
المجلّةIET Generation Transmission & Distribution
المجلّد11
العدد4
الصفحات1063-1071
الناشرInstitution of Engineering and Technology
ISSN1751-8687 · 1751-8695
DOI10.1049/iet-gtd.2016.1696
حالة النشرمنشور — 15 نوفمبر 2016